KHS Flow-Splitter unit - dynamic, for flush mounted installation

figure 650 00

  • prevents stagnation in ring pipe installations through forced flow during downstream withdrawals, can be used in cold drinking water (PWC) and hot drinking water (PWH)
  • KHS Flow-Splitter - dynamic, according to the Venturi principle, including dynamic cartridge, flow and return branch for connection of outlets / plumbing units
  • wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water

Product Features

  • prevents stagnation in ring pipe installations through forced flow during downstream withdrawals, can be used in cold drinking water (PWC) and hot drinking water (PWH)
  • KHS Flow-Splitter - dynamic, according to the Venturi principle, including dynamic cartridge, flow and return branch for connection of outlets / plumbing units
  • wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
  • KHS Flow-Splitter pass with female thread
  • plumbing unit feed pipe with female thread
  • plumbing unit return pipe with female thread
  • maintenance free
  • free from dead spots
  • including quarter turn stop valves, female threaded, for flush-mounted installation, figure 585 00
  • maintenance-free EPDM spindle seal
  • plastic shaft can be shortened
  • removable inner top part TOP-ENTRY, with EPDM gasket body and gunmetal ball
  • incl. insulation shell
  • for use in combination with DN 25 handle set

Standards and Approvals

  • valve(s) with DVGW approval
  • WRAS approval
  • according to DVGW worksheet W 570
  • according to accepted materials list from German environmental agency
  • up to DN 32 soundproofing certification according to DIN EN ISO 3822 Class 1
  • insulation shell building material class B1 according to DIN 4102
  • DIN EN 13828
  • ÜA-Reg.-Nr. R-15.2.3-21-17048, WIEN-ZERT

Technical data

  • max. installation depth 110 mm
  • pressure rating PN 16
  • max. operating temperature 90 °C
figure 650 00
Part no. passage
DN
Outlets
DN
VAV
DN
A1 A2 A3 H1
(mm)
L1
(mm)
L2
(mm)
L3
(mm)
kg
6500001500 15 15 15 Rp 1/2 Rp 1/2 Rp 1/2 48.5 185 100 84 1.76
6500002000 20 20 20 Rp 3/4 Rp 3/4 Rp 3/4 58.5 185 100 90 2.23
6500022000 20 20 15 Rp 3/4 Rp 3/4 Rp 1/2 58.5 185 100 84 2.03
6500002500 25 20 20 Rp 1 Rp 3/4 Rp 3/4 68.5 185 100 90 2.48
6500022500 25 20 15 Rp 1 Rp 3/4 Rp 1/2 68.5 185 100 84 2.22
6500003200 32 20 20 Rp 1 1/4 Rp 3/4 Rp 3/4 73.5 195 100 90 2.57
6500023200 32 20 15 Rp 1 1/4 Rp 3/4 Rp 1/2 73.5 195 100 84 2.37
6500004000 40 25 25 Rp 1 1/2 Rp 1 Rp 1 78.5 206 100 99 3.77
6500024000 40 25 15 Rp 1 1/2 Rp 1 Rp 1/2 78.5 206 100 84 2.89
6500044000 40 25 20 Rp 1 1/2 Rp 1 Rp 3/4 78.5 206 100 90 3.15
6500005000 50 25 25 Rp 2 Rp 1 Rp 1 88.5 219 100 99 4.39
6500025000 50 25 15 Rp 2 Rp 1 Rp 1/2 88.5 219 100 84 3.54
6500045000 50 25 20 Rp 2 Rp 1 Rp 3/4 88.5 219 100 90 3.88

CAD models

Part no. CAD model
6500001500 Show 3D data
6500002000 Show 3D data
6500022000 Show 3D data
6500002500 Show 3D data
6500022500 Show 3D data
6500003200 Show 3D data
6500023200 Show 3D data
6500004000 Show 3D data
6500024000 Show 3D data
6500044000 Show 3D data
6500005000 Show 3D data
6500025000 Show 3D data
6500045000 Show 3D data

Downloads

Data sheet
File type
Product datasheet
pdf
Brochures
File type
Building technology valves and systems
pdf (20.6 MB)
Brochure Hygiene System KHS
pdf (3.2 MB)
KHS Hygiene System Design Assistance
pdf (8.9 MB)
KHS Brochure for Planners
pdf (5.1 MB)
KHS Brochure for Operators
pdf (1.3 MB)
Instructions
File type
Installation and operating instructions KHS Venturi flow divider
pdf (6.9 MB)
Technical information
File type
Flow Diagram Flow-Splitter